Air Flow Transducer for laminar air flow, volume flow, temperature for duct mounting, with display, with changeover contact, 0-10 V or 4-20 mA
Description
The flow transmitter FS5020 detects the laminar air flow and the temperature in air ventilation ducts. The transmitter converts the measurement values into a linear 0-10V or 4-20mA output for further processing. As an option, a potential-free changeover contact and / or a backlit LCD display are available. In the case of display devices, the DIP switch can be used to switch to volumetric flow. For this the channel cross-sectional area must be specified in the menu. The volume flow is then calculated from the flow velocity. The content of the backlit display can be rotated by the menu in 90 ° increments. The actual value, the set switching threshold, the relay status, the MIN / MAX measured values of the selected interval, etc. can be read off. The airflow sensor works according to the calorimetric measuring principle and has 5 freely selectable scalings, which can simply be switched over as required by innovative DIP-switch technology. In addition, the switching threshold, hysteresis etc. can be specified.
Technical data
Measuring principle: | calorimetric measuring method |
Measurement range temp.: | 0...+50°C |
Measurement range flow: | 0-5 m/s |
Measurement range volume flow (calculated): | 0-65.000 m³/h |
Scales: | 0-1 m/s, 0-2 m/s, 0-3 m/s, 0-4 m/s, 0-5 m/s |
Accuracy: | ±0,3 m/s + max. ±4% FS (@ 20°C, 45% r.H., 1013 mbar), ±0,5 K (@ 20°C, > 1 m/s) |
Temperature dependency: | ±1% FS / 10 K |
Long term stability: | ±1% FS/year, ±0,2 K/year |
Response time (t90): | < 4 s @ 10 m/s |
Supply voltage: | 24 V AC/DC |
Current consumption at 0-10 V: | Ø 100 mA |
Current consumption at 4-20 mA: | < 140 mA |
Current consumption at relay: | < 120 mA |
Analogue output 0-10 V: | 3-wire connection, min. load resistance 100 kOhm |
Analogue output 4-20 mA: | 3-wire connection, max. RLoad(Ohm) = 300 Ohm |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay: | 2% of the selected scaling (without display), 0,5...5% of the selected scaling adjustable (with display) |
Electrical connection: | screw terminals max. 1,5 mm² |
Display: | optional LCD display with backlight on/off/auto |
Output attentuation: | 5 s |
Running-in time: | < 30 s at initial operation because of tempering |
Material: | Protection tube: stainless steel V2A |
Cable gland: | PG11 high-strength cable gland with strain relief |
Housing: | Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions: | Housing: L 89 x W 80 x H 47 mm, Immersion depth max.: 205 mm, Protection tube: Ø 16 mm |
Protection type: | Housing/electronic: IP65, Sensor: IP30 |
Protection class: | III |
Working range: | 0,3-5 m/s, 0...98% r.H. in contaminant-free, non-condensing air |
Working temperature: | -20...+50°C |
Storage temperature: | -20...+50°C |
Installation: | mounting flange (in scope of delivery) |
Approvals: | CE, EAC, RoHS |
Your review appreciation cannot be sent
Report comment
Report sent
Your report cannot be sent
Write your review
Review sent
Your review cannot be sent
Reference: M1200E
Brand: COMET
Reference: 514‐05
Brand: HORIBA LAQUAtwin
Reference: TR41A
Brand: TandD
Reference: TT-TQ
Brand: NESA
Reference: U0141G
Brand: COMET
Reference: RK330-01A - 4-20mA
Brand: RIKA SENSORS
Reference: T-Z03
Brand: BOSEAN
Reference: RXW-GP3A-868
Brand: ONSET
Reference: S-LIB-M003
Brand: ONSET
Reference: Y042
Brand: HORIBA LAQUAtwin
Reference: PX3PXN01S
Brand: VERIS
Reference: RK220-01
Brand: RIKA SENSORS
Reference: ME631-SD
Brand: Meatrol
Reference: DS1402D-DR8+
Brand: iBUTTON MAXIM INTEGRATED
Reference: TCR24
Brand: MAE
Reference: TAI Sensor
Brand: NESA
check_circle
check_circle