CO2-M/A Air Quality Transducer for CO2, humidity, temperature in room housing, 0-10 V
Description
Depending on the device version, the multi-sensor measuring device records the measured variables CO2 (0-2000/5000/10000 ppm), air quality VOC (low/med/high), relative humidity (0-100% RH) and temperature (0...+50°C). The transmitter converts the measured values into a standardized, analog output signal 0-10 V. As an option, the measuring device has a backlit display or LED traffic light and potential-free changeover contact. The CO2 concentration is visualized via the LED traffic light (green/yellow/red). The version with a backlit LCD display shows the measured values and min/max values of CO2, VOC, relative humidity and temperature. The switching function of the changeover contact can be defined to one of the measured variables using a DIP switch and the switching threshold can be set using a potentiometer. The CO2 concentration is measured using a non-dispersive infrared sensor (NDIR). There are 3 different CO2 scales 0-2000 ppm, 0-5000 ppm, 0-10000 ppm to choose from. The air quality is measured by a VOC sensor and detects the pollution of the ambient air by volatile organic substances such as breathing air, cigarette smoke, body vapours, material emissions, etc. The device has the setting options "low", "medium" or "high" for VOC sensitivity ". The humidity and temperature are measured by a digital sensor, which guarantees a highly accurate and long-term stable measurement result. 16 scalings are available as temperature output. The humidity output signal can be determined from the four measured variables% r.h., g / m³, g / kg and dew point temperature. The measuring device carries out an automatic calibration for CO2 and VOC at regular intervals, which ensures long-term stable measurement. This can be deactivated if necessary or performed manually on the device at any time. In addition, the measuring device has a heating function for sensor protection in the high humidity range of 95 ... 99% r.h. If the relative humidity exceeds the threshold value set ex-works for a certain period of time the heating function is activated. The sensor is heated for a limited time, thus dried and protected from condensation. During the heating and subsequent temperature compensation phase, the output signal is kept stable at the last measured value before the protective function was activated. The modern room housing has a quick-release fastener, extra-large ventilation slots, thermal decoupling and much more. The multi-sensor measuring device is ideally suited for use in workplaces, schools, living rooms, medical facilities.
Technical data
Measurement range temp.: | 0...+50°C |
Measurement range abs. humidity: | 0-50 g/m³, 0-80 g/m³ (calculated) selectable by DIP switch |
Measurement range CO2: | 0-10000 ppm, scales: 0-2000/5000/10000 ppm |
Measurement range air fuel ratio: | 0-50 g/kg, 0-80 g/kg (calculated) selectable by DIP switch |
Measurement range r.H.: | 0-100% r.H. |
Measurement range dew point: | -20...+50°C DP, -20...+80°C DP, 0...+50°C DP (calculated) selectable by DIP switch |
Measurement range VOC: | 0-100% (good / bad air quality, referring to the calibration gas) |
Accuracy: | CO2: 0-2000 ppm: ±50 ppm + 2% f. mv, 0-5000 ppm: ±50 ppm + 3% f. mv, else: ±100 ppm + 5% f. mv; VOC: ±15% FS; (20°C, 1013 mbar, Auto-Calibration ON), Humidity: ±3% r.h. (30-70% r.h., else ±5% r.h., at 20°C), Temperature: ±0,5 K |
Temperature dependency: | CO2: ±5 ppm / K, Humidity: ±0,02% r.F. / K, Temperature: ±0,05°C / 10 K |
Long term stability: | ±1% FS/year |
Sensor: | CO2: nondispersive infrared sensor (NDIR), Humidity/Temperature: combined electronic sensor, VOC: metal oxide sensor |
Response time (t90): | < 5 min |
Sensor protection: | mounted inside housing |
Supply voltage analog 0-10 V: | 24 V AC/DC (±5%) |
Current consumption: | Ø 100 mA |
Analogue output 0-10 V: | 3-wire connection |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay: | 2% FS (without Display), 0,5...5% FS adjustable (with Display) |
Electrical connection: | screw terminals max. 1,5 mm² |
Display: | traffic light display for CO2 with 3 LEDs (green/yellow/red), optional LCD display with backlight on/off/auto |
Automatic calibration: | The automatic CO2/VOC calibration takes place every 7 days, this compensates for any drifts and achieves excellent long-term stability. To ensure this function, the device must be supplied with power for at least 7 days without interruption and ventilated once with fresh air (CO2 300...400 ppm) for approx. 10 minutes within this period. For the CO2 calibration, the device saves the minimum CO2 value measured during this period internally. After 7 days, this minimum value is normalized to 400 ppm CO2 and the output signal corrected accordingly. The maximum correction is limited to half of the determined drift. If the measured value falls below approx. 300 ppm, the calibration is initialized to 400 ppm. The automatic calibration can be deactivated and performed manually if necessary. |
Pressure dependency: | CO2: 0,16% f. mv/hPa |
Running-in time: | 10 min |
Initial operation: | After switch-on of the device follows a self-test and the tempering, which takes ca. 10 minutes depending on the environmental conditions. At this time the analogue output drifts from the actual measurement value. |
Cable gland: | on the back or housing side (predetermined breaking point) |
Housing: | ABS polyman, colour signal white like RAL 9003 |
Dimensions: | Housing: L 82 x W 82 x H 25 mm |
Protection type: | IP30, IP20 (with display) |
Protection class: | III |
Working range r.H.: | 0...98% r.H. in contaminant-free, non-condensing air |
Working temperature: | 0...+50°C |
Manual calibration: | The manual CO2 calibration of the output signal to 400 ppm (zero point) is started by pressing the button on the circuit board (hold it down for approx. 5 seconds until the LED flashes). Before that, continuous operation of min. 10 minutes in fresh air. The LED is deactivated after successful calibration. The manual VOC calibration of the output signal to 1V (zero point) is started by pressing the button on the circuit board (hold down for approx. 5 seconds until the LED flashes). Before that, continuous operation of min. 2 hours with air defined as normal air quality. The LED is deactivated after successful calibration. |
Storage temperature: | -20...+50°C |
Installation: | on-wall or on flush-mounted box |
Approvals: | CE, EAC, RoHS |
Your review appreciation cannot be sent
Report comment
Report sent
Your report cannot be sent
Write your review
Review sent
Your review cannot be sent
Reference: WLB0002M
Brand: RST
Reference: S1 V2 Tempmate
Brand: tempmate
Reference: DT2485
Reference: VH400-2M
Brand: VEGETRONIX
Reference: U2422
Brand: COMET
Reference: RK300-06A
Brand: RIKA SENSORS
Reference: M1322
Brand: COMET
Reference: TT-TQ
Brand: NESA
Reference: AC-422
Brand: Apogee Instruments
Reference: DLI-600
Brand: Apogee Instruments
Reference: LS171
Brand: LINSHANG
Reference: PX3DLX01S
Brand: VERIS
Reference: K-600
Brand: BOSEAN
Reference: T5245
Brand: COMET
Reference: 57080133 1gr
Brand: FUEL CELL
Reference: PX3PLX02
Brand: VERIS
check_circle
check_circle